1989_generator_reliability — source 1989 page 1239 table II review transcription from v0.2; independent validation pending capacity_MW technology unit_count FOR MTTF_hours failure_rate_per_year MTTR_hours repair_rate_per_year maintenance_weeks_per_year 5 hydro 2 0.01 4380 2 45 198 2 10 thermal 1 0.02 2190 4 45 196 2 20 hydro 4 0.015 3650 2.4 55 157.6 2 20 thermal 1 0.025 1752 5 45 195 2 40 hydro 1 0.02 2920 3 60 147 2 40 thermal 2 0.03 1460 6 45 194 2