  "id": "1989_generation_costs",
  "source_year": 1989,
  "paper_page": 1240,
  "source_table": "IV",
  "verification": "source-transcribed; second reader check pending",
  "notes": "Table IV: capital cost shown per-unit as printed. Historical currency and economic assumptions not updated to present-day values.",
  "records": [
    {
      "unit_capacity_MW": 40,
      "technology": "hydro",
      "unit_count": 1,
      "first_merit_order": "1",
      "second_merit_order": "1",
      "FOR": 0.02,
      "fuel_cost_per_MWh": 0.45,
      "operating_cost_per_MWh": 0.05,
      "total_variable_cost_per_MWh": 0.5,
      "fixed_cost_per_kW_year": 2.5,
      "fixed_cost_total_per_year": 100000,
      "capital_cost_per_unit_USD": 160000000
    },
    {
      "unit_capacity_MW": 20,
      "technology": "hydro",
      "unit_count": 2,
      "first_merit_order": "2-3",
      "second_merit_order": "2-3",
      "FOR": 0.015,
      "fuel_cost_per_MWh": 0.45,
      "operating_cost_per_MWh": 0.05,
      "total_variable_cost_per_MWh": 0.5,
      "fixed_cost_per_kW_year": 2.5,
      "fixed_cost_total_per_year": 50000,
      "capital_cost_per_unit_USD": 80000000
    },
    {
      "unit_capacity_MW": 40,
      "technology": "lignite",
      "unit_count": 2,
      "first_merit_order": "8-9",
      "second_merit_order": "4-5",
      "FOR": 0.03,
      "fuel_cost_per_MWh": 9.5,
      "operating_cost_per_MWh": 2.5,
      "total_variable_cost_per_MWh": 12.0,
      "fixed_cost_per_kW_year": null,
      "fixed_cost_total_per_year": 790000,
      "capital_cost_per_unit_USD": 80000000
    },
    {
      "unit_capacity_MW": 20,
      "technology": "lignite",
      "unit_count": 1,
      "first_merit_order": "10",
      "second_merit_order": "6",
      "FOR": 0.025,
      "fuel_cost_per_MWh": 9.75,
      "operating_cost_per_MWh": 2.5,
      "total_variable_cost_per_MWh": 12.25,
      "fixed_cost_per_kW_year": null,
      "fixed_cost_total_per_year": 680000,
      "capital_cost_per_unit_USD": 60000000
    },
    {
      "unit_capacity_MW": 10,
      "technology": "lignite",
      "unit_count": 1,
      "first_merit_order": "11",
      "second_merit_order": "7",
      "FOR": 0.02,
      "fuel_cost_per_MWh": 10,
      "operating_cost_per_MWh": 2.5,
      "total_variable_cost_per_MWh": 12.5,
      "fixed_cost_per_kW_year": null,
      "fixed_cost_total_per_year": 600000,
      "capital_cost_per_unit_USD": 40000000
    },
    {
      "unit_capacity_MW": 20,
      "technology": "hydro",
      "unit_count": 2,
      "first_merit_order": "4-5",
      "second_merit_order": "8-9",
      "FOR": 0.015,
      "fuel_cost_per_MWh": 0.45,
      "operating_cost_per_MWh": 0.05,
      "total_variable_cost_per_MWh": 0.5,
      "fixed_cost_per_kW_year": 2.5,
      "fixed_cost_total_per_year": 50000,
      "capital_cost_per_unit_USD": 80000000
    },
    {
      "unit_capacity_MW": 5,
      "technology": "hydro",
      "unit_count": 2,
      "first_merit_order": "6-7",
      "second_merit_order": "10-11",
      "FOR": 0.01,
      "fuel_cost_per_MWh": 0.45,
      "operating_cost_per_MWh": 0.05,
      "total_variable_cost_per_MWh": 0.5,
      "fixed_cost_per_kW_year": 2.5,
      "fixed_cost_total_per_year": 12500,
      "capital_cost_per_unit_USD": 40000000
    }
  ]
}